ST PERMANENTES

DATASHEET

Category: IGA TEST
Name: IGA TEST T 25
Reference: AT-9006

PRODUCT DESCRIPTION

IGA TEST T 25 - Three-phase protector against permanent, overvoltages, with integrated MCB, nominal current 25A. Actuating time 275V→8-10s / 400V→0,1-0,2s.

Product image

IGA TEST protectors cut off the power supply when they detect a permanent overvoltage , (for example, a fault in the neutral), thus protecting the equipment installed downstream.

The protector is formed by protective coils for permanent overvoltage linked to a miniature circuit breaker (MCB).

DATASHEET

DIMENSIONS

Protector dimensions123 x 81 x 65 mm
Number of DIN modules (DIN 43880) of the protector7.00

ELECTRICALS

Nominal current25 A
Type of lineThree-phase
Maximum short-circuit current6 kA
Nominal voltage (L-N)Un230 V
Maximum overvoltage (L-N)Uc400 V
Actuation voltage V1 (L-N)Ua275 V
Actuation time at V18-10 s
Actuation voltage V2 (L-N)400 V
Actuation time (V2)0,1-0,2 s

CONSTRUCTION

FixingDIN Rail
Insulation resistance> 1014
Self-extinguishing enclosureV-0 Type according to UNE-EN IEC 60707 (UL94)
Nr. of poles4

ENVIRONMENTAL

Working temperature-5 to +40 °C
Protector locationIndoor
Enclosure protectionIP20

CONNECTION

Protector cables
Minimum / Maximum section4 / 25 mm2
ScrewPhilips, H2
Tightening3 N·m
Activation cables (S1, S2)
Minimum / Maximum section1 / 4 mm2
ScrewPhilips, H1
Tightening1.20 N·m

TESTS AND CERTIFICATIONS

Certificated tests according to the standard: UNE-EN IEC 61643-11

UNE-EN IEC 60898

UNE-EN 50550 (POP)

Relevant standards: UNE 21186, UNE-EN IEC 62305

Products compliant with EC requirements.

Diagram (mm)

INSTRUCTIONS

INSTALLATION

They must be installed in series with the low voltage line, with the input at the top of the protector.

The protective coils must be installed between the lines and the neutral at the bottom of the protector.

Image installation

SAFETY AND MAINTENANCE

Installation should be carried out without power in the line and can only be done by authorized professionals.