Lightning rod maintenance: How and when it should be done?

Lightning rods must undergo periodic inspections and maintenance, as indicated by national and international regulations (UNE21186, NF-C 17 102, IEC EN 62305). These periodic inspections of the lightning rod allow the detection of deviations from the reference standards or anomalies in the installation caused by environmental conditions such as corrosion, incorrect handling such as sectioning or robberies, or other circumstances such as expansions of the building where the lightning rod is located.

 

The inspection of the lightning protection system must be part of the maintenance routine of the buildings and the annual action plans.

Why is maintenance of lightning rods necessary?

All lightning protection systems should have routine maintenance and monitoring carried out. If the lightning rod is not properly maintained, there is a risk that lightning strikes are not controlled nor their current conducted and dispersed in a safe manner.

The different elements of the lightning protection system can be deteriorated over time, reducing safety levels of the system if they are not properly maintained.

For a lightning protection system to work optimally each and every part needs to be in good condition:

  • The lightning rods, or air terminals must work correctly. In the case of the early streamer emission (ESE), the element that emits the upward leader should be fully operational in order to maintain the time of advance of the ESE air terminal that has been measured in the laboratory. 
  • Downconductors must maintain continuity at all times and be well fixed to avoid sparks and breakage.
  • Ground resistance must remain below 10 ohms so the lightning current dissipates quickly, minimizing the return currents and the contact voltages, which that can be very dangerous for people.

lightning protection routine maintenance

How is the lightning rod revision carried out?

The procedure for the lightning rod maintenance consists of two types of verifications:

Visual inspection in the maintenance of lightning protection systems

Check that:

  • There is no damage due to lightning strikes.
  • The lightning rod keeps all its elements in good state.
  • The continuity of the conductors is correct.
  • The fixings are in good condition.
  • There are no parts damaged by corrosion.
  • The state of the equipotential bonding is correct.

Complete verification in the maintenance of the lightning protection system

The complete verification includes the visual inspections described above as well as other measures. It is necessary to verify the electrical continuity of the downconductors and the correct performance of the lightning rod according to the specifications indicated by the manufacturer.

In the case of ESEs, the correct operation of the air terminals must also be checked. The lightning rods are installed at the highest point of the structure, always two meters above any element to be protected and usually on a six-meter mast. Therefore, in most cases it is difficult to have access these air terminals and puts the operator is put in danger when carrying these inspections.

To make this maintenance task easier, Aplicaciones Tecnológicas has incorporated a remote tester to the ESE terminal DAT CONTROLER REMOTE. By doing so, it is not necessary to physically access the air terminal, since it has a system that daily checks its state and sends the result to a web application where the updated data can be consulted at any time.

Regarding the earthing system, it is essential to measure the earth resistance, as it could vary with time. It is also important to ensure that it remains below 10 Ω. It is recommended to check the earthing annually. In fact, in many countries there is a regulation that requires this. If high earth values ​​are recorded, it will be necessary to use a ground enhancing product such as Conductiver Plus or adapt the system to include more earth rods.

Likewise, the inspection must verify that the electrical lines which require protection against overvoltages are protected with adequate surge protection devices.

After having carried out the inspections described and when deterioration or anomalies in the system are detected, it is essential to repair or carry out the necessary corrective measures in the shortest time possible to ensure optimum protection.

In both periodic inspection (visual and complete) the person in charge of the maintenance actions must elaborate a report which informs the inspections that have been carried out, providing data and photographs.

lightning rod revision

When should we carry out an inspection of a lightning rod?

According to the standards, lightning protection systems must undergo an inspection whenever the structure of the building is modified or repaired and also when the structure has been struck by lightning. Therefore, it is very useful to have a lightning event counter that informs about the number of lightning strikes on the structure. For more information about the functioning of the lightning event counter check the  technical data sheet for the ATLOGGER, a device which also records the information of the day and time of the strike.

Even if these situations do not occur, the inspection of the lightning protection system should be made periodically. As part of the maintenance protocol, the following types of verifications are carried out:

  • Visual verification: Annual revision for levels of protection I and II. For levels III and IV, the visual verification needs to be done at least every two years.
  • Complete verification: For levels of protection I and II, the complete verification will be done at least every two years. For protection levels III and IV, the verification will be done at least every 4 years.
  • Complete verification of the critical systems: This verification needs to be done at least once a year for all of the protection levels.

In some countries such as Mexico and India, among others, the rainy season has high rates of precipitation and is concentrated in a very short period of the year. In these cases, it is very important to carry out the maintenance of lightning rods before the beginning of this period of the year. Contact a specialist to perform necessary lightning protection system inspection and receive appropriate advice.